Input Frequency Range
43 Hz – 65 Hz (auto detect)
Input Voltage Range
164 – 260 V AC (Wide) / 194 – 243 V AC (Narrow)
Nominal Output Voltage RMS
220 – 230 – 240 V AC
Auto Generator Start
Available
Battery Temperature Sensing
Yes, standard
Bypass Breaker Rating
80 A (230 V model)
Capable of Starting Electric Motor
12 HP
Charger Type
4-stage Power Factor Corrected (PFC) battery charger
Continuous Output Power
18 kW
Cooling
Forced air with variable-speed fans (< 60 dB @ 1 m)
Nominal Input Voltage
48 V DC
High Voltage Trip
253 V ± 4 %
High Battery Alarm / Fault
64 V DC
High DC Input Recovery
62 V DC
Relative Humidity
0 – 95 % non-condensing
Idle Consumption – Search Mode
< 60 W (Power Saver On)
Nominal Input Frequency
50 Hz or 60 Hz (auto detect)
Nominal Efficiency
> 88 % (peak)
Line Mode Efficiency
> 95 %
Low Voltage Trip
154 – 184 V ± 4 %
Low Battery Alarm
42 – 44 V DC
Low Battery Trip
40 – 42 V DC
Low Battery Voltage Recover
52 V DC
Max Input AC Voltage
270 V AC
Max Charge Rate
80 A ± 5 A
Minimum Start Voltage
40 V DC
Nominal AC Input
230 V AC
Operating Temperature
–10 °C to +40 °C (14 °F to 104 °F)
Output Frequency
50 / 60 Hz ± 0.3 Hz
Output Voltage Regulation
± 10 % RMS
Output Waveform
Pure sine wave / same as input (bypass mode)
Overcharge Protection Shutdown
63 V DC
Power Factor
0.9 – 1.0
Protection
Overload, over-temperature, short-circuit, high/low AC input, low/high battery, back-feed
Short Circuit Protection
Yes, current-limit function (fault after 1 s)
Storage Temperature
–40 °C to +70 °C (–40 °F to 158 °F)
Surge Rating (20 s)
54 kW
THD (Total Harmonic Distortion)
< 7 % typical / 10 % max under full load
Typical Transfer Time